BURKERT現(xiàn)貨庫(kù)存:

079228Q 0127-A-01,5-CC-TZ-UNFB-024/UC-03  
079229R 0127-B-01,5-CC-TZ-UNFB-024/UC-03  
079235F 0211-A-02,0-FF-MS-GM82-230/50-08  
079248U 0355-C-04,0-EF-VA-NM82-024/DC-12  
079249V 0301-C-01,0-BB-PA-FK01-230/56-02  
079264L F282-0-32,0-FF-VA-GM87-000/00-00
079264L F282-0-32,0-FF-VA-GM87-000/00-00

 

BURKERT控制器787750是一種過(guò)程和程序調(diào)節(jié)器,帶有zui多四個(gè)調(diào)節(jié)器或程序信道。裝置的規(guī)格為 144 mm x 130 mm,適合尺寸為 92 mm x 92 的 DIN 控制板凹口和 170 mm 的安裝深度。使用一個(gè) 27 色 5“ 彩色顯示器作為指示器。操作界面可自由設(shè)計(jì),根據(jù)個(gè)人喜好進(jìn)行調(diào)整。在兩個(gè)可自由配置的顯示屏界面中,可根據(jù)用戶需要放置文本、工藝值、背景圖和圖標(biāo)。zui多存在四個(gè)模擬輸入端和六個(gè)二進(jìn)制輸入端以及六個(gè)用于控制輸出端或模擬輸出端的插槽。為了通過(guò)一臺(tái)電腦進(jìn)行舒適配置,還可提供一個(gè)安裝程序。標(biāo)準(zhǔn)測(cè)量值傳感器的線性化已保存;可以對(duì)四個(gè)符合客戶要求的線性化表格進(jìn)行編程。借助于數(shù)學(xué)和邏輯模塊,可以對(duì)裝置進(jìn)行調(diào)整,使其適合各種不同的調(diào)節(jié)和控制任務(wù)。通過(guò)兩個(gè)串口 RS422/485 或 PROFIBUS-DP,可以將裝置集成安裝在一個(gè)數(shù)據(jù)聯(lián)合中。用戶可通過(guò)簡(jiǎn)單的方式加裝組件(參見(jiàn)組塊結(jié)構(gòu))。通過(guò)鎖螺絲對(duì)插式端子在背面進(jìn)行電氣連接。

 

BURKERT控制器787750特點(diǎn):
色彩鮮明的 27 色 5” 彩色顯示器
可自由配置的顯示屏界面
zui多 4 個(gè)調(diào)節(jié)器信道
對(duì)包含 1000 個(gè)節(jié)段的 50 個(gè)程序進(jìn)行動(dòng)態(tài)管理

 

BURKERT控制器7877504技術(shù)參數(shù): 

Controller structure

P, I, PD, PI, PID

PID

Control loop feedback

Proportional band

0

to 9999 digits

0 digits

Size of the proportional band

 

 

 

 

0 means that the controller structure is out of action!

Derivative time

0

to 9999 sec

80 sec

Determines the differential component of the controller output signal

Reset time

0

to 9999 sec

350 sec

Determines the integral component of the controller output signal

Cycle time

0

to 9999 sec

20 sec

When using a switched output, the cycle time should be chosen so

 

 

 

 

that the energy fl ow to the process is quasi continuous, i.e. as con-

 

 

 

 

tinuous as is practicable without overloading the switching elements

Contact spacing

0

to 999 sec

0 digits

The spacing between the two controller contacts for double-

 

 

 

 

setpoint or modulating controllers, or proportional controllers

 

 

 

 

with an integrated actuator driver

Switching differential

0

to 999 digits

1 digits

Hysteresis for switching controllers with proportional band = 0

Actuator time

5

to 3000 sec

60 sec

The actually utilized operating time of the regulator valve with

 

 

 

 

modulating controllers or proportional controllers with an integrated

 

 

 

 

actuator driver

Working point

-100

to +100%

0%

The output level for P and PD controllers (if x = w then y = Y0)

Output level limiting

0

to 100%

100%

The maximum limit for the output level

 

-100

to +100%

-100%

The minimum limit for the output level

Minimum relay ON time

0

to 60 sec

0 sec

Limits the frequency of switching for switched outputs